Logical Nodes For Switchgear. Ln Group: X - GE 350 Communications Manual

Protective relay platform
Hide thumbs Also See for 350:
Table of Contents

Advertisement

3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
2.5.3 MMTR
MMTR: Metering
MMTR class
Attribute Name
Attr.
Type
MMTR_0
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Measured values
PosTotWh
MV_5
NegTotWh
MV_5
PosTotVArh
MV_5
NegTotVArh
MV_5

2.6 Logical Nodes for switchgear. LN Group: X

2.6.1 XCBR (Circuit breaker)
XCBR: circuit breaker
XCBR class
Attribute Name
Attr.
Type
XCBR
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Loc
SPS_0
OpCnt
INS_2
Controls
Pos
DPC_0
BlkOpn
SPC_1
BlkCls
SPC_1
Status information
CBOpCap
INS_4
Explanation
M/O/C/E Notes
Metering
Mode
M
Behaviour
M
Health
M
Name plate
M
E
E
E
E
Explanation
M/O/C/E Notes
Circuit breaker
Mode
M
Behaviour
M
Health
M
Name plate
M
Local operation
M
Operation counter
M
Switch position
M
Block opening
M
Block closing
M
Cicruit breaker operating
O
capability
Local / Remote
Breaker openings
Breaker open, close
A–31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

339345

Table of Contents