3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
GGIO7: Analog Operands logical node.
GGIO class
Attribute Name
Attr. Type Explanation
GGIO_5
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Measured Values
AnIn1
MV_0
AnIn2
MV_0
..
..
AnIn8
MV_0

2.5 Logical Nodes for metering and measurement. LN Group: M

2.5.1 MMXU
MMXU1: measurements (339/350).
MMXU class
Attribute Name
Attr. Type Explanation
MMXU_0
Data
Common Logical Node Information
Mod
INC_0
Beh
INS_0
Health
INS_1
NamPlt
LPL_1
Measured values
TotW
MV_0
TotVAr
MV_0
TotVA
MV_0
TotPF
MV_0
Hz
MV_0
PPV
DEL_0
PhV
WYE_0
A
WYE_1
AuxV
CMV_1
M/O/C/E Notes
Generic process I/O
Mode
M
Behaviour
M
Health
M
Name plate
M
Analog Operand 1
O
Analog Operand 2
O
..
..
Analog Operand 8
O
M/O/C/E Notes
Measurement
Mode
M
Behaviour
M
Health
M
Name plate
M
Total active power (P)
O
Total reactive power (Q)
O
Total apparent power (S)
O
Average power factor (PF) O
Line Frequency
O
Phase to phase voltages
O
(VL1L2,...)
Phase to ground voltages
O
(VL1ER, ...)
Phase currents (IL1, ...)
O
Auxiliary Phase Voltage
E
A–27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

339345

Table of Contents