General Maintenance - GE MI-869 Instruction Manual

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

GENERAL MAINTENANCE

General Maintenance
In-service Maintenance
Out-of-service Maintenance
FASTPATH:
Unscheduled Maintenance (System Interruption)
8–6
The 869 requires minimal maintenance. As a microprocessor-based relay, its
characteristics do not change over time. The expected service life of a 869 is 20 years
when the environment and electrical conditions are within stated specifications.
While the 869 performs continual self-tests, it is recommended that maintenance be
scheduled with other system maintenance. This maintenance can involve in-service, out-
of-service, or unscheduled maintenance.
1.
Visual verification of the analog values integrity, such as voltage and current (in
comparison to other devices on the corresponding system).
2.
Visual verification of active alarms, relay display messages, and LED indications.
3.
Visual inspection for any damage, corrosion, dust, or loose wires.
4.
Event recorder file download with further events analysis.
1.
Check wiring connections for firmness.
2.
Analog values (currents, voltages, RTDs, analog inputs) injection test and metering
accuracy verification. Calibrated test equipment is required.
3.
Protection elements setting verification (analog values injection or visual verification
of setting file entries against relay settings schedule).
4.
Contact inputs and outputs verification. This test can be conducted by direct change
of state forcing or as part of the system functional testing.
5.
Visual inspection for any damage, corrosion, or dust.
6.
Event recorder file download with further events analysis.
To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-
energized state once per year, for one hour continuously.
View the event recorder and oscillography for correct operation of inputs, outputs, and
elements.
CHAPTER 8: MAINTENANCE