Communications

GOOSE Rx and Tx
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
The 869 supports 3 GOOSE transmissions and 8 GOOSE receptions each with 64 items per
transmission or reception. Non-structured GOOSE is supported. Each item within the
GOOSE message can be a digital or analog value. Messages are launched within one scan
of a digital point status change or an analog exceeding its deadband. The 869 supports a
total of remote digital outputs.
The 869 server supports a subset of the server features described in part 7.2 of the
IEC61850 standard.
GOOSE MESSAGING
As indicated above, the 869 supports 3 GOOSE transmissions and eight GOOSE receptions
as shown in the table below:
Service
Launch
Support for
Speed*
Programmable
time to live
Configurab
Within 2 ms
Time to live
le GOOSE
(1 CPU
programmable
scan)*
from 1000 to
60000 ms
* Launch speed is measured by comparing the time stamp in SOE of digital remote output
status change to the time stamp of message seen on the network by a computer who's
clock is synchronized by an IRIG-B card to the same IRIG-B source as the 869 relay.
REMOTE INPUTS
Path:
Status > Communications > Remote Inputs
The present state of the 32 remote inputs are shown here. The state displayed is the
remote point unless the remote device has been established to be "Offline" in which case
the value shown is the programmed default state for the remote input.
GGIO1 INDICATIONS
Path:
Status > Communications > GGIO1 Indications
The present state of the 32 GGIO1 Indications are shown here. There are up to 32 GGIO
indications that can be used to map any FlexLogic operand into the IED 61850 information
model. Default value is Off.
GOOSE STATUS
Path:
Status > Communications > GOOSE STATUS
GOOSE 1 to 8 Status
Range: OFF, ON
Default: OFF
GOOSE HEADER
Path:
Status > Communications > GOOSE HDR STATUS
GOOSE 1 to 8 H.Status
Range: OFF, ON
Default: OFF
IEC 61850 STATUS
Path:
Status > Communications > IEC 61850 STATUS
# of Tx
# of Rx
Test Bit
Support
3
8
Y
Devices
COMMUNICATIONS
Number of
Number of
items in
remote
each
inputs per
transmissi
relay
on or
reception
64 Data
32
Items per
Data Set
5–7

Advertisement

Table of Contents
loading

This manual is also suitable for:

869

Table of Contents