FLEXLOGIC

FlexElements

4–362
There are 8 identical FlexElements™. A FlexElement is a universal comparator, that can be
used to monitor any analog actual value measured or calculated by the relay, or a net
difference of any two analog actual values of the same type. Depending on how the
FlexElement is programmed, the effective operating signal could be either a signed signal
("Signed" selected for Input Mode), or an absolute value ("Absolute" selected for Input
Mode).
The element can be programmed to respond either to a signal level or to a rate-of-change
(delta) over a pre-defined period of time. The output operand is asserted when the
operating signal is higher than a threshold or lower than a threshold as chosen by the user.
When programming a FlexElement, one must keep in mind the following limitations:
1.
The analog inputs for any FlexElement must be from the same "gender":
current and current (in any combination, phase-symmetrical, phase-phase, kA-A,
differential, restraint, etc.)
voltage and voltage (as above)
active power and active power (Watts and Watts)
reactive power and reactive power (Vars and Vars)
apparent power and apparent power (VA and VA)
angle and angle (any, no matter what signal, for example angle of voltage and
angle of current are a valid pair)
% and % (any, for example THD and harmonic content is a valid pair)
V/Hz and V/Hz
°C and °C
2
2
I
t and I
t
FlexElement actual and FlexElement actual
For all the other combinations, the element displays 0.000 or N/A and will not assert
any output operand.
2.
The analog value associated with one FlexElement can be used as an input to another
FlexElement "Cascading".
Figure 4-146: FlexElement logic diagram
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS