Chapter 5: Status
Motor
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Status
Figure 5-1: Main Status Screen
The motor start screen is shown as follows.
Path:
Status > Motor
MOTOR STATUS: STOPPED
Range: Tripped, Stopped, Starting, Running, Overload
Default: Stopped
These messages describe the motor status at any given point in time. All motor status
operands are mutually exclusive.
Motor Stopped and Tripped conditions are detected based on the current level and
switching device status (52a or 52b). For the case when switching device is not
configured (i.e., setpoints Contact Input 52a or Contact Input 52b are set to "Off" under
5–1