8.2
Testing (the analog loop)
Primary loop / transfer route
Primary loop : 121
Escape
Fig. 83: Testing the analog loop
Enter the number of the analog loop to be tested and press the Select function key.
Enter the number of the desired function (3 = Testing) or select the menu options >Test operation< with the
cursor keys and press the >Function< key.
An analog loop in test operation will not signal an alarm in the case of an event!
The Function >Testing< is not carried out when ...
the analog loop is switched off.
the analog loop module is defective.
Testing an analog loop
The test operation must be carried out individually for each analog loop or detector zone. The simultaneous
testing of several analog loops/detector zones is impossible.
By this menu point, the selected analog loop (including all detectors and esserbus
detector zones in the analog loop are tested for the following functions:
Malfunctions of one or more detectors / esserbus
Malfunction of the switch-on control (SOC) by automatic detectors.
Conformance of the addresses with the Customer data programming
(if necessary, the detector data is automatically updated).
Conformance of the analog loop wiring with the Customer data programming.
Conformance of detector types and external wiring with the Customer data programming.
FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
1 Switch on / reset
2 Switch off
3 Test
4 Replace detector
Function
®
transponders.
®
transponders) or single
99