Honeywell IQ8Control C Installation Instruction page 119

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Trouble
Possible Cause
Code No.
There are more detectors on the
069
loop than programmed in the
customer data.
Error during detector data
070
allocation.
This detector change may only
be performed with the service PC
080
because this detector required
customer data that cannot be
generated in the panel itself.
An OTI-detector has been
installed at detector location. The
081
sensor type has changed in
comparison with the customer
data.
An OT-detector has been
installed at detector location. The
082
sensor type has changed in
comparison with the customer
data.
An I-detector has been installed
at detector location. The sensor
083
type has changed in comparison
with the customer data
A TM-detector has been installed
at detector location. The detector
084
type has changed in comparison
with the customer data.
A TME-detector has been
installed at detector location. The
085
detector type has changed in
comparison with the customer
data.
A TD-detector has been installed
at detector location. The detector
086
type has changed in comparison
with the customer data.
A O-detector has been installed
at detector location. The detector
087
type has changed in comparison
with the customer data.
Detector circuitry has been
changed at detector location.
088
Now detector has neither
external circuit (relay / LED) nor
isolating relay.
Detector circuitry has been
changed at detector location.
089
Now detector has external circuit.
(relay / LED).
Detector circuitry has been
changed at detector location.
090
Now detector has an isolating
relay.
FB 798951.GB0 / 01.09
Fire Alarm Control Panel IQ8Control C/M
1st. measure
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Check whether detector type
change is desired; if it is,
activate analog loop.
Check whether detector type
change is desired; if it is,
activate analog loop
Check whether detector type
change is desired; if it is,
activate analog loop.
Check whether detector type
change is desired; if it is,
activate analog loop.
Check whether detector type
change is desired; if it is,
activate analog loop.
Check whether detector type
change is desired; if it is,
activate analog loop.
If this change is not desired,
connect service PC and run
a configuration check.
Re-program customer data.
Check whether this detector
location is to have an
external circuit. isolating
relay. If it is, activate loop.
Check whether this detector
location has an isolating
relay. If it has, activate loop.
2nd. measure
---
---
---
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
---
Otherwise install detector you
require and re-start >Detector
change<
Otherwise install detector you
require and re-start >Detector
change<
119