Fire Alarm Control Panel IQ8Control C/M
4 Relay module (Part No. 787536)
Four dry relay contacts (not monitored) with programmable
operation mode normally open or normally close.
Contact rating: max. 30 V DC / 1A
Quiescent
current: approx. 10 mA.
Total current per module max. 1 A
®
essernet
module 62.5 kBd (Part No. 784840 / 784840.10)
network module for max. 16 network devices;
telephone cable IY (ST) Y x 2 x 0.8mm
Cable length between two devices max. 1000 m
Quiescent
current: approx. 170 mA.
®
essernet
module 500 kBd (Part No. 784841 / 784841.10)
network module for max. 31 network devices; cable IBM type 1 or
similar cables;
Cable length between two devices max. 1000 m
Quiescent
current: approx. 150 mA.
94
1 2
ext. device to relay K 1
ext. device to relay K 2
ext. device to relay K 3
ext. device to relay K 4
1 2
L 1+
L 1-
L 2+
L 2-
not used
not used
not used
not used
FB 798951.GB0 / 01.09
3 4 5
6
7 8
7 8
3 4 5
6