Earth fault monitoring
BR 1
Earth fault monitoring enabled (factory default = ON)
Earth fault monitoring disabled (not VdS appropriate)
Information for powered loop systems
In case of an earth fault with +U
message "U
zone
is lower than the required 42 V. The audible alarm loop device may not sound an alarm at full
volume.
Undervoltage protection (U
BR2
Undervoltage protection activated (factory setting = ON)
The panel switches off automatically if, in case of charging, the
battery voltage is ≤ 9.5 DC.
Under voltage protection disabled
Selection of the analog loop voltage
BR 4
®
esserbus
System with 27,5 V analog loop voltage
®
esserbus
PLus System with 42 V analog loop voltage
®
esserbus
PLus module Part No. 80 4382 and appropriate loop
devices with Part No. 80 xxxx required
Damage to the system !
Mixed operation with esserbus
Selection of the Fire Alarm Control Panel
Solder jumper on the rear side of the PCP to select the CPU power supply voltage.
BR5
Factory default of a separately delivered power supply module
(Prepared for mounting in the FACP 8000 C / M)
Operation in FACP IQ8Control C/M
FB 798951.GB0 / 01.09
a ground fault message occurs and additionally the fault
zone
<" will be displayed for each analog loop. In the alarm condition, the zone voltage
< 9,5 V DC)
Batt
®
and esserbus
Fire Alarm Control Panel IQ8Control C/M
®
PLus functionality is not possible!
Jumper BR 5 closed
ON
1 2 3
OFF
1 2 3
1
ON
2
3
1
2
OFF
3
3 2 1
3 2 1
BR5
BR5
27