Honeywell IQ8Control C Installation Instruction page 52

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C/M
Operating mode 1
Relay K1 positive switching and monitored
R *
680
K1
NO
K1
*
V
Fig. 46: Terminal of the master box relay K1
BR8
BR7
BR6
Relay K1
3
3
3
positive switching (+12 V DC
2
2
2
1
1
1
Monitored end-of-line resistor R = 680 Ω (factory setting) Monitoring capability of
R*
internal resistor in master box 50 to 1000 Ω (refer to customer data programming)
S*
Dry confirmation contact in master box
*
Diode V
From Hardware index B the diode V
52
S*
NC
C
*
is integrated in the Field device module.
/ max. 1A) and monitored
intern
FB 798951.GB0 / 01.09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iq8control m

Table of Contents