Setting the essernet
address
The address of Network Micro Modules type 1 and 2 with hardware revision E and higher is set as a decimal
number by means of two rotary switches. Use an appropriate screwdriver for setting switches S1 (x1) and S2
(x10). The actual address is represented by the total of both values.
Adressing example e.g. Panel, address 9 or 21
Micro module
address
0
9
2
21
Jumper configuration for the essernet
®
If an essernet
micro module is used in the micro module slot, the integrated EMC filter must be set with
jumpers X27 to X30.
All jumpers in horizontal position
X27 X28 X29 X30
All jumpers in vertical position
X27 X28 X29 X30
EMC protection of the essernet
FB 798951.GB0 / 01.09
Schalterstellung
S2
S1
9
1
®
micro module type
®
cabling has to be ensured by appropriate external devices.
Fire Alarm Control Panel IQ8Control C/M
Address factor
S1 = X 1
S2 = X 10
S1 = X 1
S2 = X 10
Required configuration for all micro modules apart from
®
essernet
(factory setting)
EMC protection for this micro module connection terminal is
activated
Only required for essernet
The EMC protection is activated on the micro module for
®
essernet
and therefore switched off on the
basic module.
Value
Σ = S1 x 1 + S2 x 10
9 x 1 + 0 x 10 = 9
1 x 1 + 2 x 10 = 21
®
micro module.