Fire Alarm Control Panel IQ8Control C/M
CPU failure mode function of relays K2, K3 and K4
K4
Fig.51: Location of the emergency mode jumpers BR3 to 5 on the Field device module
K2
K3
3
3
2
2
1
1
3
3
2
2
1
1
56
K3
K2
3
2
1
K4
Jumper X in position 1/2
3
2
No activation of the relay while the Fire Alarm Control
Panel is in CPU failure mode (state on leaving factory).
1
3
Jumper X in position 2/3
2
Relay also activated while the Fire Alarm Control Panel is
in CPU failure mode.
1
Used if a common function is programmed for the relays,
such as >common fire<, >common alarm< and >common
disconnection<.
FB 798951.GB0 / 01.09