Honeywell IQ8Control C Installation Instruction page 103

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

8.5
Simulation of control states
Under this menu point, the state of any control, such as relays or open collectors, can be simulated for test
purposes. The simulation of control states in an essernet
exclusively to controls which are allocated to this Fire Alarm Control Panel and are programmed in the customer
data with a control zone number, such as:
Relay or open collectors of the micro modules of these FACP
Detector base outputs of intelligent fire detectors Series 9100
Detector base outputs of intelligent fire detectors Series 9200 / IQ8Quad
Controls of esserbus
With the simulation of a control state, all programmed displays and controls for this control and state are
activated or deactivated. (Observe customer data programming).
Control simulation
:
Control
Status
Fig. 87: Entering the control number
Control simulation
: 15
Control
Status
Selecting a function
Fig. 88:
Enter the control number of the corresponding open collector or relay
Press the Select function key
Enter the number for the desired function ( 1 = Activate, 2 = Trouble, 3 = End test) or select with the cursor
keys and press the function key >function< to acknowledge the input
To end this simulation, each individual control whose operating state has been simulated must be terminated
with the End test function!
For the master box controls (Control numbers 1 to 10), a simulation is impossible! Simulation of
individual detectors or zones is not supported via communications transponder (Part No. 808615) of
the 8010 extinguishing control system.
FB 798951.GB0 / 01.09
®
transponders in the analog loop
Activation
Trouble
End test
Repeat
1
Activation
2 Trouble
3 End test
Fire Alarm Control Panel IQ8Control C/M
®
network is impossible. The function pertains
*
By pressing the >Repeat< key,
the displayed control number is
incremented by the value "+1"
without the need of entering the
new (next higher) control number
Select
on the keyboard.
Function
103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iq8control m