Honeywell IQ8Control C Installation Instruction page 48

Fire alarm control panel
Hide thumbs Also See for IQ8Control C:
Table of Contents

Advertisement

Fire Alarm Control Panel IQ8Control C/M
Relay for connecting a master box. May also be used as a freely programmable relay.
Relay K1
Selection of operating mode and emergency function by means of jumpers.
(Monitoring range 50 Ω to 1 k Ω )
Contact rating when used as a >non-monitored change-over contact<
< 30 V DC/ max.1 A
Relay K2,3,4
Relay with common function. May also be used as a freely programmable relay.
Selection of operating mode and emergency function by means of jumpers.
Contact rating when used as a >non-monitored change-over contact<
< 30 V DC/ max. 2A
X4
8 inputs for connecting a fire department operating panel – top – IN 1-8
8 outputs for connecting a fire department operating panel – bottom – OUT 1-8
Connection terminals for (master box relay, K1)
X5
for connecting the master box supply voltage, incl. confirmation input for verifying master
box activation
X6
Connection terminal for relay K2
Connection terminal for relay K3
X7
X8
Connection terminal for relay K4
GR1 = Internal primary loop input (primary line no. XX24, XX= FACP no.)
Normal operation
Fire alarm
Trouble
X9 / X10
Terminals for the micro module slot (only Field device module Part No. 772477)
T1A – Fuse for Relay K1
F1
F2 to F4
T2A – Fuse for Relay K2, K3, K4
V8, V10,
The LED lights while the corresponding relay is activated or when is has been programmed
V11, V12
for inverse control in the customer data programming
V20 to V22
yellow LED V 20
green LED V 21
red
BR1 and BR2
Solder bridges for setting the master box control in emergency operation
BR3 to BR5
Jumpers for setting the CPU failure mode function for relays K2, K3, K4
BR6 to BR20
Jumper to select the operation mode of relay K1 and relays K2, K3, K4
BR21
Coding jumpers for fire department operating panel with >fire control off / revision< function
(Terminals X4/IN8)
Jumper in position 2-3
Jumper in position 1-2
Do not connect relays (AE) of the FACP IQ8Control with alternating voltage. Even in the case of a
>potential free relay< mode it is not possible to switch an external AC-voltage.
48
will light up when the Fire Alarm Control Panel is operating in
CPU failure mode
will light up when the cover contact (control panel housing) is
open
LED V 22
will light up if a fire alarm is detected while the control panel is
operating in CPU failure mode
>fire control off / revision<
not active / off (factory setting)
>fire control off / revision<
active / on
R = 10 k Ω
R ≤ 5 k Ω
R = 1 k Ω
FB 798951.GB0 / 01.09