Wiring Details 301ADI
Wall Mount Installation

Wiring Instructions

1. Disconnect power supply before proceeding to connect any wiring.
2. Connect the communication wires from the controller's (301C) RS-
485 port into communication terminals A and B (J1).
3. Connect the transmitter wires to the analog inputs (J2, J4), in SIG
and VDC OUT.
4. Connect the contact device to the digital inputs (J5).
When all connections are complete, you can proceed to the
configuration of the unit.