Basic Guidelines

Follow these instructions to the letter to ensure that the equipment will
function properly. Failure to respect these guidelines will release
Honeywell Analytics from any responsibility in the event of improper
functioning:
Make sure to locate all transmitters in areas easily accessible for
service.
Avoid locations where instruments are subject to vibrations
Avoid locating transmitters near sources of electromagnetic
interference
Avoid locating transmitters in areas subject to significant
temperature swings
Transmitters should be installed 1.5 m (5 ft.) above the floor for CO
transmitters to prevent signal interference by vehicles ( NO
transmitters should be installed 30 cm [1 ft] from the ceiling.)
Install transmitters in upright position (to ensure ease of use and
access to programming pushbuttons).
Place transmitters so that they are facing the center of the area
Do not install a transmitter facing a parking space; the vehicle will
sever the communication link. If possible, install the transmitter
perpendicular to the space.
Avoid installing the transmitters on or near metal (transformers,
pipes, etc.)
Do not install transmitters on ceilings
Do not install transmitters in ceiling or wall wells (placement in
these areas may impede signal transmission)