C7735A1000 Duct Air
Temperature Sensor
APPLICATION
The C7735A1000 Duct Air Temperature Sensor (DATS)
is a duct-mounted temperature probe used to sense
discharge air temperature in zoning applications for high
and low temperature limit protection. Alternatively, it is
used with certain Honeywell thermostats for delta-T
diagnostics and IAQ control. For more on these
applications, please see the installation instructions for
those products.
2-7/16 (62)
2-7/16
(62)
Fig. 1. C7735A dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
IMPORTANT
Do not locate the DATS probe in a duct near the
heat exchanger or strip heat, which can cause
false temperature readings.
1-1/32
(26)
3-15/16 (100)

INSTALLATION INSTRUCTIONS

1. Assemble the DATS by attaching the metal sensor
probe to the plastic cap. Insert the plate of the
probe into the two tabs on the inside bottom of the
cap. Then rotate the plate clockwise until it clicks
into the single top tab.
2. Locate the DATS on the supply trunk between the
bypass damper and the evaporator coil and/or heat
exchanger. If a bypass damper is not used, locate
the DATS between the zone dampers and the
evaporator coil and/or heat exchanger. See Fig. 2.
BY PASS DAMPER
PLACE SENSOR
INTHIS AREA.
M33115
Fig. 2. DATS mounting location.
3. Drill a 1/4 in. hole in the duct at the location
selected for the sensor.
4. Attach wire using wire nuts and push them into the
cover, then insert the probe into the hole drilled in
step 2.
5. Secure the DATS to the side of the duct, through
the two mounting holes, with the screws supplied.
IMPORTANT
Use 18-22 gauge thermostat wire for shorter
runs. For longer runs or when wiring near volt-
age, use shielded cable.
6. Run wire to zone panel or thermostat. See zone
panel or thermostat installation instructions.
ZONE DAMPERS
DO NOT
EVAPORATOR COIL
PLACE
SENSOR IN
THIS AREA.
HEAT EXCHANGER
BLOWER
69-1521EFS-01
M14877A

Advertisement

loading

Summary of Contents for Honeywell C7735A1000

  • Page 1: Installation Instructions

    Insert the plate of the probe into the two tabs on the inside bottom of the The C7735A1000 Duct Air Temperature Sensor (DATS) cap. Then rotate the plate clockwise until it clicks is a duct-mounted temperature probe used to sense into the single top tab.
  • Page 2 C7735A1000 DUCT AIR TEMPERATURE SENSOR Table 1. DATS Resistance Cross Reference. Temperature (°F) Resistance Temperature (°F) Resistance Temperature (°F) Resistance Temperature (°F) Resistance 10514 3830 1582 33630 10253 3747 1552 32668 10000 3666 1523 31737 9754 3587 1494 30835 9514...
  • Page 3: Notice D'installation

    Faire ensuite tourner la plaque dans le sens horaire jusqu’à ce qu’elle s’enclenche dans la languette supérieure unique. Le capteur de température d’air de gaine C7735A1000 2. Placer le capteur de température d’air de gaine sur est une sonde de température montée en gaine utilisée le bloc d’alimentation entre le registre de dérivation...
  • Page 4 CAPTEUR DE TEMPÉRATURE D’AIR DE GAINE C7735A1000 Tableau 1. Valeurs des résistances du capteur de température d’air de gaine. Température (°F) Résistance Température (°F) Résistance Température (°F) Résistance Température (°F) Résistance 10514 3830 1582 33630 10253 3747 1552 32668 10000...
  • Page 5: Instrucciones De Instalación

    El sensor de temperatura de aire del conducto (DATS) 2. Ubique el DATS en el circuito de suministro entre el C7735A1000 es una sonda utilizada para detectar la regulador desviador y el serpentín del evaporador temperatura del aire de descarga en aplicaciones de y/o el intercambiador de calor.
  • Page 6 SENSOR DE TEMPERATURA DE AIRE DEL CONDUCTO C7735A1000 Tabla 1. Referencia cruzada de la resistencia del DATS. Temperatura (°F) Resistencia Temperatura (°F) Resistencia Temperatura (°F) Resistencia Temperatura (°F) Resistencia 10514 3830 1582 33630 10253 3747 1552 32668 10000 3666 1523...
  • Page 7 SENSOR DE TEMPERATURA DE AIRE DEL CONDUCTO C7735A1000 69-1521EFS—01...
  • Page 8 SENSOR DE TEMPERATURA DE AIRE DEL CONDUCTO C7735A1000 Automatización y control desenlace Honeywell International Inc. 1985 Douglas Drive North ® Marca Registrada en los Estados Unidos © 2011 Honeywell International Inc. todos Golden Valley, MN 55422 Los Derechos Reservados 69-1521EFS—01 M.S.