WIRING DETAILS

- Observe proper polarity.
- If not using the integrated EOL resistors, set all switches to
OFF.
- If using the integrated EOL resistors:
1. Connect the sensor to the panel (see wiring diagrams
below).
2. Set the appropriate tamper [RT], alarm [RA] and trouble [RF]
DIP switches to ON (see
Wiring Examples
Alarm, Tamper and
Trouble configured
to one loop.
Alarm, Tamper and
Trouble configured
to two loops.
RA = Alarm EOL resistor
RT = Tamper EOL resistor
1. Close the sensor and apply power to the sensor. Initialization is
complete when the LED stops flashing slowly (about 30 seconds).
2. Walk through the detection area and observe the LED.
3. Adjust the microwave range as necessary to meet installation requirements.
Walk test mode is active for 10 minutes, then automatically exits test mode,
disables the LED and enters normal operation mode. For an additional 10
minute walk test, enable walk test mode again with the
following page).
Step 4
on page 2).
RF = Trouble EOL resistor
W1 = 1 and 2 loop connection resistor.
Notes:
- Consult the Control Panel manual to determine
proper EOL selection.
- The Alarm, Tamper and Trouble EOL settings must
each only have one switch ON.
- The EOL values should be set at the same time.
LED
Red
Yellow
Green
flashlight feature
(see the
- 3 -
Walk Test
Power Up
Normal
[10 min.]
Slow
ON
ON
Blink
Alarm
Alarm
ON
OFF
OFF
Microwave
ON
OFF
OFF
PIR
Notes:
- During power up and walk test
modes the LED is active
regardless of the
LED
Enable/Disable DIP switch
- When the
microwave sensitivity
set to minimum, the sensor range
is reduced to 5m.
Fault
Fast
Blink
OFF
OFF
setting.
is