4.7.2

Wiring and Terminal Connections

NOTES:
1. Cable shield must be grounded at one end only, at the Control Panel. Coil and tape cable shield
at the Detector end.
2. Set SW3 (rotary switch) to position one (1) for Source current wiring.
3. Set SW3 (rotary switch) to position zero (0) for Sink current wiring.
Honeywell
Figure 4-5
Typical Wiring for 4-20mA (Sourcing) Analog Output
Figure 4-6
Typical Wiring for 4-20mA (Sinking) Analog Output