B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 54 of 60)
ADDR
REGISTER NAME
CAE1
Direct Input/Output Ch 1 Unreturned Messages
Alarm Msg Count
CAE2
Direct Input/Output Ch 1 Unreturned Messages
Alarm Threshold
CAE3
Direct Input/Output Ch 1 Unreturned Messages
Alarm Events
CAE4
Reserved (4 items)
CAE8
Direct Input/Output Ch 2 Unreturned Messages
Alarm Function
CAE9
Direct Input/Output Ch 2 Unreturned Messages
Alarm Msg Count
B
CAEA
Direct Input/Output Ch 2 Unreturned Messages
Alarm Threshold
CAEB
Direct Input/Output Channel 2 Unreturned
Messages Alarm Events
CAEC
Reserved (4 items)
Remote Devices (Read/Write Setting) (16 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID
(GOID)
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
CB23
Remote Device 1 in PMU Scheme
CB24
Reserved
CB25
...Repeated for Device 2
CB4A
...Repeated for Device 3
CB6F
...Repeated for Device 4
CB94
...Repeated for Device 5
CBB9
...Repeated for Device 6
CBDE
...Repeated for Device 7
CC03
...Repeated for Device 8
CC28
...Repeated for Device 9
CC4D
...Repeated for Device 10
CC72
...Repeated for Device 11
CC97
...Repeated for Device 12
CCBC
...Repeated for Device 13
CCE1
...Repeated for Device 14
CD06
...Repeated for Device 15
CD2B
...Repeated for Device 16
Remote Inputs (Read/Write Setting) (32 modules)
CFA0
Remote Input 1 Device
CFA1
Remote Input 1 Bit Pair
CFA2
Remote Input 1 Default State
CFA3
Remote Input 1 Events
CFA4
Remote Input 1 Name
CFAA
...Repeated for Remote Input 2
CFB4
...Repeated for Remote Input 3
CFBE
...Repeated for Remote Input 4
CFC8
...Repeated for Remote Input 5
CFD2
...Repeated for Remote Input 6
CFDC
...Repeated for Remote Input 7
CFE6
...Repeated for Remote Input 8
CFF0
...Repeated for Remote Input 9
B-62
RANGE
100 to 10000
1 to 1000
0 to 1
1 to 1000
0 to 1
100 to 10000
1 to 1000
0 to 1
1 to 1000
---
0 to 16383
0 to 16
0 to 1
0 to 3
1 to 32
0 to 96
0 to 3
0 to 1
1 to 64
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
---
F209
---
1
F001
---
1
F184
---
1
F126
---
1
F626
---
1
F001
---
1
F156
---
1
F086
---
1
F102
---
1
F205
DEFAULT
600
10
0 (Disabled)
10
0 (Disabled)
600
10
0 (Disabled)
10
"Remote
Device 1"
0
0 (Fixed)
0 (No)
0 (None)
1
0 (None)
0 (Off)
0 (Disabled)
"Rem Ip 1"
GE Multilin

Advertisement

Table of Contents
loading