5.8 INPUTS AND OUTPUTS
c) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE/GOOSE MESSAGES
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE DEVICE
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
For
REMOTE DEVICE 1 ID
correctly.
The
REMOTE DEVICE 1 ETYPE APPID
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The
REMOTE DEVICE 1 DATASET
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
5
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic oper-
ands. However, GGIO3 data can be read by IEC 61850 clients.
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE INPUT 1
Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originat-
ing in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of
UserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE/GOOSE
message. A user must program a DNA point from the appropriate FlexLogic operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The
REMOTE INPUT 1 ID
selects the remote device which originates the required signal, as previously assigned to the remote device via the setting
REMOTE DEVICE (16) ID
GSSE/GOOSE message required.
5-184
REMOTE DEVICES
1
REMOTE DEVICE
Remote Device 1
REMOTE DEVICE
MESSAGE
ETYPE APPID: 0
REMOTE DEVICE
MESSAGE
DATASET: Fixed
, restart the unit when you change this setting to ensure that the Online or Offline status displays
setting is only used with GOOSE messages; they are not applicable to GSSE mes-
setting provides for the choice of the B30 fixed (DNA/UserSt) dataset (that is, containing
REMOTE INPUTS
REMOTE INPUT
Remote Ip
REMOTE IN
MESSAGE
Remote Device
REMOTE IN
MESSAGE
None
REMOTE IN
MESSAGE
STATE: Off
REMOTE IN
MESSAGE
EVENTS: Disabled
setting allows the user to assign descriptive text to the remote input. The
(see the Remote devices section). The
B30 Bus Differential System
REMOTE DEVICE 1(16)
Range: up to 20 alphanumeric characters
1 ID:
Range: 0 to 16383 in steps of 1
1
Range: Fixed, GOOSE 1 through GOOSE 16
1
REMOTE INPUT 1(32)
Range: up to 12 alphanumeric characters
1 ID:
1
Range: Remote Device 1 to Remote device 16
1 DEVICE:
1
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
1 ITEM:
Config Item 1 to Config Item 32
Range: On, Off, Latest/On, Latest/Off
1 DEFAULT
Range: Disabled, Enabled
1
setting selects the specific bits of the
REMOTE IN 1 ITEM
5 SETTINGS
5.8.6 REMOTE INPUTS
setting
REMOTE IN 1 DEVICE
GE Multilin