APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 60)
ADDR
REGISTER NAME
5A0C
Phase Instantaneous Overcurrent 1 Events
5A0D
Reserved (6 items)
5A13
...Repeated for Phase Instantaneous Overcurrent
2
5A26
...Repeated for Phase Instantaneous Overcurrent
3
5A39
...Repeated for Phase Instantaneous Overcurrent
4
5A4C
...Repeated for Phase Instantaneous Overcurrent
5
5A5F
...Repeated for Phase Instantaneous Overcurrent
6
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
5B04
Neutral Time Overcurrent 1 Curve
5B05
Neutral Time Overcurrent 1 Multiplier
5B06
Neutral Time Overcurrent 1 Reset
5B07
Neutral Time Overcurrent 1 Block
5B09
Neutral Time Overcurrent 1 Target
5B0A
Neutral Time Overcurrent 1 Events
5B0B
Reserved (6 items)
5B11
...Repeated for Neutral Time Overcurrent 2
5B22
...Repeated for Neutral Time Overcurrent 3
5B33
...Repeated for Neutral Time Overcurrent 4
5B44
...Repeated for Neutral Time Overcurrent 5
5B55
...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting (6 modules)
5C00
Neutral Instantaneous Overcurrent 1 Function
5C01
Neutral Instantaneous Overcurrent 1 Signal
Source
5C02
Neutral Instantaneous Overcurrent 1 Pickup
5C03
Neutral Instantaneous Overcurrent 1 Delay
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
5C05
Neutral Instantaneous Overcurrent 1 Block
5C07
Neutral Instantaneous Overcurrent 1 Target
5C08
Neutral Instantaneous Overcurrent 1 Events
5C09
Reserved (8 items)
5C11
...Repeated for Neutral Instantaneous Overcurrent
2
5C22
...Repeated for Neutral Instantaneous Overcurrent
3
5C33
...Repeated for Neutral Instantaneous Overcurrent
4
5C44
...Repeated for Neutral Instantaneous Overcurrent
5
5C55
...Repeated for Neutral Instantaneous Overcurrent
6
GE Multilin
RANGE
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
---
0.01
F001
---
1
F104
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (Disabled)
0
B
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
0 (IEEE Mod
Inv)
100
0
(Instantaneou
s)
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
B-35