GE B30 UR Series Instruction Manual page 461

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 41 of 60)
ADDR
REGISTER NAME
AB09
Operand for IEC 61850 XCBR4.ST.Loc Status
AB0B
Command to Clear XCBR4 OpCnt (Operation
Counter)
AB0C
Operand for IEC 61850 XCBR5.ST.Loc Status
AB0E
Command to Clear XCBR5 OpCnt (Operation
Counter)
AB0F
Operand for IEC 61850 XCBR6.ST.Loc Status
AB11
Command to Clear XCBR6 OpCnt (Operation
Counter)
IEC 61850 LN Name Prefixes (Read/Write Settings)
AB30
IEC 61850 Logical Node LPHD1 Name Prefix
AB33
IEC 61850 Logical Node PIOCx Name Prefix (72
items)
AC0B
IEC 61850 Logical Node PTOCx Name Prefix (24
items)
AC53
IEC 61850 Logical Node PTUVx Name Prefix (13
items)
AC7A
IEC 61850 Logical Node PTOVx Name Prefix (10
items)
AC98
IEC 61850 Logical Node PDISx Name Prefix (10
items)
ACB6
IEC 61850 Logical Node RBRFx Name Prefix (24
items)
ACFE
IEC 61850 Logical Node RPSBx Name Prefix
AD01
IEC 61850 Logical Node RRECx Name Prefix (6
items)
AD13
IEC 61850 Logical Node MMXUx Name Prefix (6
items)
AD25
IEC 61850 Logical Node GGIOx Name Prefix (5
items)
AD34
IEC 61850 Logical Node RFLOx Name Prefix (5
items)
AD43
IEC 61850 Logical Node XCBRx Name Prefix (6
items)
AD55
IEC 61850 Logical Node PTRCx Name Prefix (6
items)
AD67
IEC 61850 Logical Node PDIFx Name Prefix (4
items)
AD73
IEC 61850 Logical Node MMXNx Name Prefix (37
items)
ADE2
IEC 61850 Logical Node CSWIx Name Prefix (30
items)
AE3C
IEC 61850 Logical Node XSWIx Name Prefix (24
items)
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write Setting)
AF00
Number of Analog Input Points in GGIO4
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules)
AF10
IEC 61850 GGIO4 Analog Input 1 Value
AF11
IEC 61850 GGIO4 Analog Input 1 Deadband
AF13
IEC 61850 GGIO4 Analog Input 1 Minimum
AF15
IEC 61850 GGIO4 Analog Input 1 Maximum
AF17
...Repeated for IEC 61850 GGIO4 Analog Input 2
AF1E
...Repeated for IEC 61850 GGIO4 Analog Input 3
AF25
...Repeated for IEC 61850 GGIO4 Analog Input 4
AF2C
...Repeated for IEC 61850 GGIO4 Analog Input 5
GE Multilin
RANGE
0 to 65535
0 to 1
0 to 65535
0 to 1
0 to 65535
0 to 1
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
4 to 32
---
0.001 to 100
–1000000000000 to
1000000000000
–1000000000000 to
1000000000000
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F300
---
1
F126
---
1
F300
---
1
F126
---
1
F300
---
1
F126
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
1
F206
---
4
F001
---
---
F600
%
0.001
F003
---
0.001
F060
---
0.001
F060
DEFAULT
0
0 (No)
0
0 (No)
0
0 (No)
(none)
B
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
(none)
4
0
100000
0
1000000
B-49

Advertisement

Table of Contents
loading

Table of Contents