Advertisement

5 SETTINGS
The
IEC ------- DEFAULT THRESHOLD
M_ME_NC_1 analog data. These settings group the B30 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the B30 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the B30, the default thresholds are in effect.
The
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,
IEC REDUNDANCY
two simultaneous connections can be active at any given time.
When the IEC port number is set to 0, the change takes effect when the B30 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
NOTE
those protocols.
The B30 relay does not support power metering. As such, the
cable.
NOTE
The B30 relay does not support energy metering. As such, the
cable.
NOTE
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to "Enabled", the DNP protocol does not operate. When this setting is changed, it takes effect when
power to the relay is cycled (off-to-on).
NOTE
PATH: SETTINGS
PRODUCT SETUP
ADDRESSES
 IEC NETWORK
 CLIENT ADDRESSES
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The UR can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the UR can connect.
A maximum of two simultaneous connections are supported at any given time.
m) EGD PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 EGD PROTOCOL
MESSAGE
MESSAGE
GE Multilin
settings are used to determine when to trigger spontaneous responses containing


COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
0.0.0.0
CLIENT ADDRESS 3:
0.0.0.0
CLIENT ADDRESS 4:
0.0.0.0
CLIENT ADDRESS 5:
0.0.0.0


COMMUNICATIONS
EGD PROTOCOL
 FAST PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 2
 CONFIGURATION
B30 Bus Differential System
IEC CURRENT DEFAULT THRESHOLD
IEC POWER DEFAULT THRESHOLD
IEC ENERGY DEFAULT THRESHOLD

IEC 60870-5-104 PROTOCOL
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
5.2 PRODUCT SETUP
set-
setting is not appli-
setting is not appli-
IEC NETWORK CLIENT
5
5-45