Table 6-9 Restore Factory Calibration - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Input Calibration
Step
Operation
Set LOCKOUT to
1
NONE
Enter INPUT 1
2
Setup Group
Scroll through
3
Functions
4
Return to Normal
Operation
52

Table 6-9 Restore Factory Calibration

Press
until you see:
SET UP
Upper Display = SET UP
Lower Display = LOCK
Until you see:
FUNCTION
Upper Display = one of the following:
NONE – all parameters are read/write
CAL - all parameters are read/write except Calibration
CONF – configuration parameters are Read Only; no
writes permitted
+SP – Only the Lockout group is available for read/write.
Setpoint value is Read Only.
Lower Display = LOCK
[ ] [ ]
Until NONE is in the upper display
until you see:
SET UP
Upper Display = SET UP
Lower Display = INPUT 1
until you see:
FUNCTION
Upper Display = the current selection
Lower Display = IN1TYP
to change the current selection to another selection
[ ] [ ]
until the lower display rolls through the rest of the functions
FUNCTION
and returns to
Upper Display = the new selection
Lower Display = IN1TYP
until you change the input selection in the upper display back
[ ] [ ]
to the proper selection. You will see:
Upper Display = Original Input Selection that matches your
type of sensor.
Lower Display = IN1TYP
to return to Normal operating mode.
DISPLAY
The factory calibration will be restored. If the problem is not
corrected, contact the provider.
UDC2300 Limit Controller Product Manual