Alarms Set Up Group

Introduction
An alarm is an indication that an event that you have configured (for example—Process
Variable) has exceeded one or more alarm limits. There are two alarms available. Each
alarm has two setpoints. You can configure each of these two setpoints to alarm on
various controller parameters.
There are two alarm output selections, High and Low. You can configure each setpoint to
alarm either High or Low. These are called single alarms.
You can also configure the two setpoints to alarm on the same event and to alarm both
high and low. A single adjustable Hysteresis of 0 to 100% is configurable for the alarm
setpoint.
See Table 2-4 in the Installation section for Alarm relay contact information.
The prompts for the Alarm Outputs appear whether or not the alarm relays are physically
present. This allows the Alarm status to be shown on the display and/or sent via
communications to a host computer.
Function Prompts
Prompt
Description
AxSxVA
Alarm Setpointx
Value
A1S1
X = 1 or 2
A1S2
A2S1
A2S2
AxSxTY
Alarmx Setpointx
Type
A1S1
X = 1 or 2
A1S2
A2S1
A2S2
Alarmx Setpoint
AxSxHL
State
A1S1
X = 1 or 2
A1S2
A2S1
A2S2
1/01

Table 4-8 ALARMS Group Function Prompts

This is the value at which you want the alarm type
chosen in Prompt "AxSxTY" to actuate. The value
depends on what the alarm setpoint has been
configured to represent.
Range of Setting:
within the range of the selected parameter or of
the PV Span for Deviation configurations
Select what you want Setpoint x of Alarm x to
represent; it can represent the Process Variable or
Deviation.
NONE
PROC
DE
SHED
PVRT
DI
Select whether you want the alarm type chosen in
prompt "AxSxTY" to alarm High or Low.
LOW
HIGH
UDC2300 Limit Controller Product Manual
Selection or Range of Setting
No Alarm
Process Variable
Deviation
Shed Communications (Shed alarms do
not have setpoint values)
PV Rate of Change
Alarm on Digital Input
Low Alarm
High Alarm
Configuration
Factory
Setting
90
NONE
HIGH
31