Honeywell TH8320R1003 Vision Pro 8000 Product Data page 74

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
MULTIPLE DRY CONTACT DEVICES
ON ONE SET OF TERMINALS
1. Wire the dry contact device to S1–S4 terminals at the
EIM.
2. Enter Installer Setup (see "Make Changes to Installer
Setup" beginning on page 19).
3. Dry Contacts are selected at ISU 600. Select the appro-
priate Dry Contact(s) and press Next.
4. Select the terminals wired to the Dry Contact device, and
press Next.
5. Select Normally Open or Normally Closed, and press
Next.
NOTE: For example, if a wet switch is normally open, it
will close when the device detects water. If the
wet switch is normally closed, it will open when
the device detects water.
Refer to the instructions packed with the dry
contact device to determine if it is normally
open or normally closed.
68-0312—01
ONE DRY CONTACT DEVICE
S4
S4
S3
S3
Fig. 156. Wiring dry contact devices.
Fig. 157.
Fig. 158.
EIM
EIM
6. If you are creating a custom alert, type the alert name
and press Done. The alert name is what appears on the
Home screen when the alert is detected. See Fig. 160.
You can edit or confirm the alert name after you enter it.
7. Type the custom alert message and press Done. The
custom alert message appears after selecting the alert
and pressing "View More Info". See Fig. 161. You can
edit or confirm the alert message after you enter it.
74
ONE DRY CONTACT DEVICE
MULTIPLE DRY CONTACT DEVICES
ON ONE SET OF TERMINALS
Fig. 159.
Fig. 160.