VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
313
Radiant Cycles
Per Hour Stage 1
Note: "Stage 1" is
stage of Radiant
Heat.
313
Radiant Cycles
Per Hour Stage 2
314
Cool /
1 to 6 CPH
Compressor
stage.
314
Cool /
1 to 6 CPH
Compressor
Cycles Per Hour
Stage 2
68-0312-01
Table 2. Installer Setup (ISU) Table. (Continued)
3
3
3
3
30
Residential,
Commercial
Requires
Heating Equipment is Geothermal Radiant.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Both
Yes
This ISU is only displayed when ISU 201
Heating Equipment is Geothermal Radiant.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
This ISU is only displayed when ISU 207 Cool
/ Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Both
No
This ISU is only displayed when ISU 207 Cool
/ Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Notes