ISU
Installer Setup
Number
Name
610
Water Leak Alert
Normally Open
is [See Settings]
Normally Closed
611
Shutdown Alert
None
S1
S2
S3
S4
612
Shutdown Alert is
Normally Open
[See Settings]
Normally Closed
613
Service Alert
None
S1
S2
S3
S4
614
Service Alert is
Normally Open
[See Settings]
Normally Closed
615
Fan Failure Alert
None
S1
S2
S3
S4
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Normally Open Both
None
Normally Open Both
None
Normally Open Both
None
45
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects water.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects water.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the System
Shutdown Dry Contact Device.
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Service
Needed Dry Contact Device.
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Fan Failure
Dry Contact Device.
®
8000 WITH REDLINK™
Notes
68-0312—01