Both No; Cycles Per Hour; Stage 1; Note: "Stage 1" Is - Honeywell TH8320R1003 Vision Pro 8000 Product Data

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
316
Backup Heat
1 to 12 CPH

Cycles Per Hour

Stage 1

Note: "Stage 1" is

not displayed if

there is only 1

stage.
316
Backup Heat
1 to 12 CPH
Cycles Per Hour
Stage 2
324
Compressor Off
Off
Time
1 - 5 minutes
326
Extended Fan Run
0, 30, 60, 90 seconds, 2, 3, 4, 5,
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
Time in Cool
minutes
326
Extended Fan Run
0, 30, 60, 90 seconds, 2, 3, 4, 5,
6, 7, 8, 9, 10, 11, 12, 13, 14, 15
Time in Heat
minutes
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Electric =
9 CPH
Gas / Oil =
5 CPH
Electric =
9 CPH
Gas / Oil =
5 CPH
5 minutes
0 seconds
0 seconds
33
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 207 or
213 Backup Heat Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Both
No
This ISU is only displayed when ISU 207 or
213 Backup Heat Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Both
No
The thermostat has a built in compressor
protection (minimum off timer) that prevents
the compressor from restarting too early after
a shutdown. The minimum-off timer is
activated after the compressor turns off.
If there is a call during the minimum-off timer,
the thermostat shows "Wait" in the display.
Both
No
After the call for cooling ends, the thermostat
keeps the fan on for the selected amount of
time for increased efficiency. This may re-
introduce humidity into the living space.
Both
No
After the call for heating ends, the thermostat
keeps the fan on for the selected amount of
time for increased efficiency.
®
8000 WITH REDLINK™
Notes
68-0312—01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th8321r1001 vision pro 8000Th8110r1008 vision pro 8000

Table of Contents