Honeywell TH8320R1003 Vision Pro 8000 Product Data page 24

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
222
A-L/A Terminal
None
Time Of Day
Economizer
Heat Pump Fault
300
System
Manual
Changeover
Automatic
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
None
Manual:
if ISU 101 is
Residential
Automatic:
if ISU 101 is
Commercial
24
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
This ISU is only displayed when ISU 101
Application is Commercial.
Note: When the thermostat is setup for
Residential, the L/A terminal operates as
described under "Heat Pump Fault". The L/A
terminal requires no setup for residential
applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is energized
during Occupied periods and when the user
overrides the temperature. The terminal is de-
energized during Unoccupied periods and in
Standby mode.
Economizer: The thermostat controls an
economizer module to provide ventilation
during Occupied periods and free cooling
when outdoor conditions are favorable. The
A-L/A terminal is energized during Occupied
periods and during a call for cooling in
Unoccupied periods. See "Economizer and
Time of Day (TOD) Operation" beginning on
page 105.
Notes: The economizer module determines
when outdoor conditions are favorable for free
cooling.
Heat Pump Fault: When 24 volts is detected
on the L/A terminal (compressor monitor), the
thermostat displays a message to alert the
user when the heat pump requires service.
The L/A terminal sends a continuous output to
a zone panel when the thermostat is set to
Emergency Heat mode. The zone panel will
not turn on the heat pump when a zone is set
to Emergency Heat mode.
Both
No
Manual: The user must select heating or
cooling as needed to maintain the desired
indoor temperature.
Automatic: The user has the option to select
Auto for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.
Notes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th8321r1001 vision pro 8000Th8110r1008 vision pro 8000

Table of Contents