ISU
Installer Setup
Number
Name
913
Dehum Fan
Tstat Controls Fan
Control
Equip Controls Fan
914
Run Dehumidifier
Yes
when Cool is On
No
918
Dehum Away
Not Allowed
Mode
Allowed
919
Dehum Away
Automatic
Mode Fan Setting
On
Circulate
920
Dehum Away
70° F to 80° F
Mode Low Limit
Temp
920
Dehum Away
70° F to 99° F
mode Temp
Setting
920
Dehum Away
40% to 70% (in 5% increments)
mode Dehum
Setting
921
Dehumidifier Filter
Off
Reminder
30, 60, Calendar Days
3 to 12 Calendar Months (in 1
month increments)
1000
Ventilation Type
None
ERV / HRV
Passive (Fan Only)
Fresh Air Damper
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Tstat Controls
Fan
Yes
Not Allowed
Automatic
76° F
85° F
65%
Off
None
51
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 900
Dehum Equipment is set to Dehumidifier.
Tstat Controls Fan: The thermostat turns on
the dehumidifier and the fan when
dehumidification is needed.
Equip Controls Fan: The thermostat turns on
the dehumidifier when dehumidification is
needed. The fan is controlled by the
equipment.
Both
No
This ISU is only displayed when ISU 900
Dehum Equipment is set to Dehumidifier.
Yes: Dehumidifier can run when the cooling
system is on.
No: Dehumidifier can NOT run when the
cooling system is on.
Both
No
This ISU is NOT displayed when ISU 900
Dehum Equipment is None.
ISU 919 to 920 are only displayed when ISU
918 Dehum Away Mode is Allowed.
See "Dehumidification Away Mode" beginning
on page 84.
Both
No
The On and Circulate settings may re-
introduce humidity into the living space.
Both
No
If the cooling system is used to control
humidity while Dehumidification Away Mode
is active, the thermostat allows the cooling
system to lower the indoor air to the Low
Limit Temperature Setting to reach the
dehumidification setting at ISU 920.
Both
No
The temperature maintained while
Dehumidification Away Mode is active and the
desired humidity level is satisfied.
Both
No
The desired humidity level while
Dehumidification Away Mode is active.
Both
No
Both
No
None: The thermostat does not control
ventilation.
ERV/HRV: The thermostat controls an Energy
Recovery Ventilator or Heat Recovery
Ventilator for ventilation.
Passive (Fan Only): The thermostat turns on
the fan for ventilation.
Fresh Air Damper: The thermostat turns on
the fan and opens a fresh air damper for
ventilation.
®
8000 WITH REDLINK™