VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
408
Max. Cool
Off
Recovery Ramp
1° F/hr to 20° F/hr
Rate
408
Max. Cool
Off
Recovery Outdoor
-20° F to 100°F
Temp
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
6° F/hr
70° F
38
Residential,
Commercial
Requires
or Both
EIM
Commercial
No
Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
Commercial
No
Off: The cooling system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the cooling system can
recover at for a mild day in your region.
Default setting is 6° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate.
The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and
save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
Notes