Honeywell TH8320R1003 Vision Pro 8000 Product Data page 40

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
413
Residential:
None
Entry / Exit
40° F to 90° F
Remote - Away
Heat Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote -
Unoccupied Heat
Setpoint
414
Residential:
None
Entry / Exit
50° F to 99° F
Remote - Vacation
Cool Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote - Holiday
Cool Setpoint
414
Residential:
None
Entry / Exit
40° F to 90° F
Remote - Vacation
Heat Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote - Holiday
Heat Setpoint
500
Wired Sensor on
No
S Terminals
Yes
500
Wired Remote
No
Indoor Sensor
Yes
500
Wired Outdoor
No
Sensor
Yes
500
Wired Return
No
Sensor
Yes
500
Wired Discharge
No
Sensor
Yes
501
Indoor Sensor
[Select Indoor Sensor Name]
Name
502
Indoor Sensor
None
S1
S2
S3
S4
68-0312—01
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
65° F
82° F
60° F
No
No
No
No
No
Indoor Sensor Both
None
40
Residential,
Commercial
Requires
or Both
EIM
Both
No
The thermostat maintains this Heat setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 109.
Both
No
The thermostat maintains this Cool setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 109.
Both
No
The thermostat maintains this Heat setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 109.
Both
No
This ISU is only displayed if an S1–S4
terminal is available.
Both
No
The thermostat will not display the Wired
Remote Indoor Sensor option if 6 wireless
indoor air sensors are already connected to
the thermostat. If you have a wired Indoor Air
Temperature network (1, 4, 9 etc), the
thermostat will allow up to 5 wireless indoor
air sensors.
Both
No
The thermostat will not display the Wired
Outdoor Sensor option if a wireless outdoor
air sensor is already connected to the
thermostat.
Both
Yes
The thermostat will not display the Wired
Return Sensor option if there is no fan in the
system.
Both
No
The thermostat will not display the Wired
Discharge Sensor option if there is no fan in
the system.
No
Select a name (location) of the Wired Remote
Indoor Sensor.
Both
No
Select the terminals wired to the Remote
Indoor Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and
S4
Notes