Toshiba GR200 Series Instruction Manual page 539

Hide thumbs Also See for GR200 Series:

Advertisement

Input
Command "Remote-On-Control"
510001_7001016D08
DEV01_CONTROL_REQ
ILK† condition ("ON") passed
SPOS01-On
User configurable condition
(PLC#1 connection point)
510001 810101EE57
SPOS01IN_TMP_35
User configurable condition
(PLC#2 connection point)
510001 810101EDDA
SPOS01IN_TMP_42
ASEQ function§" is in progress
ASEQ_MULTI_SEL
Figure 4.1-20 Operate 'On' logic by remote SAS in SPOS01
†Note: The ILK function can provide the operation criteria for "ON".
‡Note: An "operate condition" signal is generated in the operate-condition logic (see
Figure 4.1-29) when Fixlogic is set for scheme switch [SPOS01-LGCTRCON]. If an
alternative "Operate-condition" is required, it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative "Operate-condition" can be connected to the above logic using
connection point #1 "User configurable condition". That is, set the scheme switch
[SPOS01-LGCTRCON] to PLC and use "SPOS01IN_TMP_38".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of the output signal. When Var is set for scheme switch
[SPOS01-PLSM], the output period of the signal is defined by the setting
[SPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
When Latch is set, the output signal is kept issuing until the reception of
"Command Off".
Note: To identify the input and output signal-points of the other SPOS logics, see Table
††
4.1-14 for PLC#1, Table 4.1-15 for PLC#2, Table 4.1-19, and Table 4.1-20 for
output signals.
Note: The "Operate failed" signal is issued when the state-change is not detected when
‡‡
the time set by [SPOS01-RST] has been reached.
Operate logic in SPOS01
SPOS01 function (Function ID: 510001)
Operate Cmd.
&
with ILK
condition
Operation Cmd.
without ILK
condition
[SPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[SPOS01-LGCFEXOT]
Fixedlogic
[SPOS01-PLSM]*
Var
Fix
Latch
"SPOS01-EX_CMP"
(5A0101_8001011E93)
"SPOS01-FEX_BO"
(510001_8101011DD0)
- 518 -
"
SPOS01-OEC_OK_CSF"
(510001_8001011E7F)
1≥
1≥
&
&
&
&
&
6F2S1915 (0.46)
Output
[SPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
S
R
To BO connection
"SPOS01_OEX_BO"
(510001_8201011DD3) §§
&
Assign to BOs
To PLC
&
logic
PLC#2
To "Wait for a command"
"
SPOS01_EX_FFL
[SPOS01-RST]
(510001_8601011E91)
0
t
1.0s- 100.0s
Operation Failed
††
GRZ200 (Soft 031 & 032)
"
††