Stub protection with overcurrent relay (STUB-OC)
Figure 2.11-1 illustrates a one-and-a-half breaker (1.5CBs) arrangement with a transmission
line including a disconnector (DS). An area 'stub zone' is defined within two CBs and the DS,
which is expressed by hatching in the figure.
For the 1.5CB arrangement, a voltage transformer (VT) is generally installed along the
line GH. The figure shows that the line GH is taken out of service because of the DS being
open; hence, a distance relay in the IED_G cannot detect a fault when a fault occurs in the
'stub' zone. This is because a faulted voltage cannot be measured correctly using the VT G .
Thereby, an overcurrent relay (OC) is provided to protect the 'stub' zone and the OC relay
operates speedy upon occurrence of the fault.
CT1
CB1
CB2
CT2
Line
CB
Terminal-G
─────────────────────────────────────────────────────────────────
Note:
The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the "G&T position" referring to the
comparison table below. For more information, see
Table 2.11-1 Comparative table in respective ordering numbers
✓: Applicable
G
G
Fault
DS
VT
G
G
IED_G
G
Figure 2.11-1 Fault occurred in stub zone
Sec.
Feature
Main features
NA: Not applicable
Line GH
IED_H
Appendix: Ordering
Ordering No. at "G&T"
31
32
- 233 -
6F2S1915 (0.46)
CT1
H
CB1
H
CB2
VT
H
H
CT2
H
Line
CB
Terminal-H
.
GRZ200 (Soft 031 & 032)