Download Print this page

Toshiba GR200 Series Instruction Manual page 226

Hide thumbs Also See for GR200 Series:

Advertisement

OCN(Function ID:443001)
Setting items
TOCN1R
OCN1-RTMS-
ORG
OCN1-k
OCN1-a
OCN1-c
OCN1-kr
OCN1-b
Output
OCN1-2fBlk
OCN1-VTFBlk
OCN1-CTFBlk
OCN1-UseFor
OCN1-ARCBlk
OCN2
OCN2-Dir
Fwd/
OCN2-Angle
Rev
OCN2-Vpol
OCN2-Timer
DT
OCN2
OCN2-DPR
TOCN2
IEC
OCN2
OCN2-DPR
OCN2-TMS-
IEC
TOCN2R
UK
OCN2
OCN2-DPR
OCN2-TMS-
UK
TOCN2R
IEEE
OCN2
OCN2-DPR
OCN2-TMS-
IEEE
OCN2-Rtimer
TOCN2R
OCN2-RTMS-
IEEE
US
OCN2
OCN2-DPR
OCN2-TMS-US
OCN2-Rtimer
TOCN2R
Range
Unit
1A rating
5A rating
0.00 - 300.00
s OCN1 definite time reset delay
OCN1 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OCN1 user original curve coefficient
0.00000 - 10.00000
- OCN1 user original curve coefficient
0.00000 - 10.00000
- OCN1 user original curve coefficient
0.00000 - 500.00000
- OCN1 user original curve coefficient
0.00000 - 10.00000
- OCN1 user original curve coefficient
Non / Block
- OCN1 operation block by 2f-detection
Non / Block
- OCN1 operation block by VTF
Non / Block
- OCN1 operation block by CTF
Trip / Alarm
- OCN1 used for trip or alarm
Non / Block
- Autoreclose block by OCN1
NonDir / Forward /
- OCN2 directional characteristic
Reverse
0 - 180
deg OCN2 directional characteristic angle
0.5 - 25.0
V OCN2 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OCN2 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 -
0.10 -
A OCN2 threshold (in DT mode)
50.00
250.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.00 - 300.00
s OCN2 operating delay time
0.02 -
0.10 -
A OCN2 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of IEC inverse curve
0.00 - 300.00
s OCN2 definite time reset delay
0.02 -
0.10 -
A OCN2 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of UK inverse curve
0.00 - 300.00
s OCN2 definite time reset delay
0.02 -
0.10 -
A OCN2 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of IEEE inverse curve
DEF / DEP
- OCN2 reset delay type of IEEE
0.00 - 300.00
s OCN2 definite time reset delay
OCN2 dependent reset time multiplier of
0.010 - 50.000
-
IEEE inverse curve
0.02 -
0.10 -
A OCN2 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OCN2 drop-out/pick-up ratio
0.010 - 50.000
- OCN2 time multiplier of US inverse curve
DEF / DEP
- OCN2 reset delay type of US
0.00 - 300.00
s OCN2 definite time reset delay
- 205 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Non
Trip
Block
NonDir
45
3.0
DT
0.40
2.00
100
1.00
0.40
2.00
100
1.000
0.00
0.40
2.00
100
1.000
0.00
0.40
2.00
100
1.000
DEF
0.00
1.000
0.40
2.00
100
1.000
DEF
0.00

Advertisement

loading

This manual is also suitable for: