Download Print this page

Toshiba GR200 Series Instruction Manual page 419

Hide thumbs Also See for GR200 Series:

Advertisement

Collection: The signals, received from the various protection functions (shown as
'FC18' and others; see Table 2.26-2 and Table 2.26-6), are gathered in the Trip-signal
collection logic.
Generation: CB trip signal generation, Sub-signal generation for blocking ARC§, and
Alarm-signal generation logics are provided.
A binary output (BO†) circuit must be selected in order to energize the trip coil of the
CB#1 and CB#2. That is, the BOs should be made the connection with the CB#1 and CB#2 trip
coils; the drive signal should be outputted (i.e., 'TRIP-COMMAND1-A,-B,-C' and 'TRIP-
COMMAND2-A,-B,-C'†). The Alarm-signal generation logic operates to provide a trigger signal
for the recording function‡.
†Note: The internal connection between the TRC function and the BIO module should be
performed using the BIO settings or the PLC programming. The user can program
the connection the PLC monitoring point 'TRIP-COMMAND1-A (8000001B20) etc.'
with preferred BO circuits using the settings [Input signal1] etc. of each BO on the
BIO module. The externally wired connection between the BIO module and trip
coil circuit is made at the IED terminals. For more information with regard to the
BO circuit concerning the Element ID (Data ID), see Chapter
description: Binary IO module
§Note: Autoreclose (ARC) and other protection functions are discussed separately. See
Relay application
Chapter
‡Note: For information on recording, see
.
, respectively.
Chapter Recording function
- 398 -
6F2S1915 (0.46)
Technical
.
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200