Toshiba GR200 Series Instruction Manual page 528

Hide thumbs Also See for GR200 Series:

Advertisement

Signals from user PLC logic
OFF-control command requiring ILK† checking
(PLC#1 connection point)
510001 800101EE31
DEV01_OP_INTERLOCK
ILK† condition ("OFF") passed
OFF-control command requiring no ILK† checking
(PLC#2 connection point)
510001 800101EE30
DEV01_OP_COMMAND
Figure 4.1-12 Selection logic for 'Off' by PLC in SPOS01
†Note: The software interlocking (ILK) function can provide the operation criteria for
"Off". The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
Note: To identify the input and output points of the other SPOS logic, see Table 4.1-3
††
for the input (PLC#1 and PLC#2) and Table 4.1-9 for the outputs.
Output signal to BO
The SPOS01 function, in Figure 4.1-12, can issue a "Select success" signal at the output point
"SPOS01_FSL_BO_CSF"
Note: The output point "SPOS01_FSL_BO_CSF" is the same signal as shown in Figure
1
4.1-4.
Select condition
(vii)
Figure 4.1-13 shows the select condition logic in the SPOS01 function. The SPOS01 function
checks the condition for the select command using the signal "SPOS01_STATE" (Table 4.1-25).
If the original logic does not meet with the requirements of the user, the following alternatives
are available:
1. The user can replace the original logic with alternative logic.
2. The user can add additional logic to the original logic.
How to add another select condition signal
If adding another condition is required, the user can add a signal to the select condition logic
using the PLC connection point "User Additional condition".
1. Add a user-preferred signal using SPOS01IN_TMP_31, which is listed as PLC#1 in
Table 4.1-7.
SPOS01 function (Function ID: 510001)
For DIR operation
Operate command with
ILK† condition
SPOS01-Off
For DIR operation
Operate command
without ILK† condition
PLC in DIR operate
Select condition‡
.
1
- 507 -
Select logic in SPOS01
1≥
&
&
6F2S1915 (0.46)
Output
&
To BO connection
"SPOS01_FSL_BO_CSF"
(510001_8601011DC6)
0
t
Selection "success"
0.1s
To "Wait for a command"
0
t
Selection "Failed"
0.6s
††
GRZ200 (Soft 031 & 032)