Download Print this page

Toshiba GR200 Series Instruction Manual page 716

Hide thumbs Also See for GR200 Series:

Advertisement

V1 V2
DS1
Figure 4.6-19 Bus-bar arrangement and PLC setting
Voltage selection should be considered in accordance with the arrangement of VTs.
Voltages V1 and V2
respectively. Consequently, V-L1 and V2-L1 are set for the scheme switches [SyncRy1-VR] and
[SyncRy1-VI], respectively. Table 4.6-8 shows the setting example for this arrangement.
Setting Name
Description
SyncRy1-VR
Selection of running voltage
SyncRy1-VI
Selection of incoming voltage
SyncRy2-VR
Selection of running voltage
SyncRy2-VI
Selection of incoming voltage
Busbar#1
Busbar#2
DS1 closed
DS2 closed
DS2
S43P logic programmed
CB1
by the user
represent the running voltage (V R ) and the incoming voltage (V I ),
Table 4.6-8 Setting example
- 695 -
&
SYNC01_RY1_USE_STS
Selection of SYNCHK_Ry1
SYNCHK01 and 02 functions
Default
V-L1
Either of V-L1 / V-L2 / V-L3
V2-L1
Either of V2-L1 / V2-L2 / V2-L3
N.A
N.A
N.A
N.A
6F2S1915 (0.46)
Setting item or value
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200