Mapping output data
(ii)
The user should group the OPTIM signals with regard to GOOSE and REPORT; the user
should map them for the IEC61850 communication using the GR-TIEMS. Figure 4.4-15 shows
how to map a signal; it shows that the signals of the OPTIM function are required to map for
the IEC61850 communication.
Object_reference
Ctrl/GGIO3302$SPCSO1$origin
Ctrl/GGIO3302$SPCSO1$origin
Ctrl/GGIO3302$SPCSO1
Ctrl/GGIO3302$SPCSO1
Ctrl/GGIO3302$SPCSO1
Ctrl/GGIO3302$SPCSO1
Note:
"Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.4-15 orCat attribute mapped into SPCSO object of GGIO3302
Mapping input data
(iii)
The OPTIM function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point "OPTR 01_CONTROL_REQ". Table 4.4-6 shows the input-point
"OPTR01_CONTROL_REQ" and the Object reference "Ctrl/GGIO3302$SCPSO" ; the user should
Table 4.4-5 Mapping signals for SPC object
Attribute
Type
orCat
orCategory
orIdent
Octet64
stVal
BOOLEAN
Q
Quality
T
Timestamp
stSeld
BOOLEAN
- 657 -
FC
Signal Number
529001 200C011008
ST
529001 310C01170A
ST
529001 310C011EA1
ST
301001 3110041005
ST
200301 9010001006
ST
529001 000C011D90
ST
6F2S1915 (0.46)
Signal Name
OPTR01_ORCAT
OPTR01_ORIDENT
OPT_RST_CMD
Qual_Val
SYS_TIME
OPTR01_STSELD
GRZ200 (Soft 031 & 032)