It is advantageous to connect Motor Modules with different pulse frequencies to different
DRIVE-CLiQ sockets of the Control Unit. They may also be connected at the same DRIVE-
CLiQ line.
In the following diagram, two Motor Modules (400 V, output ≤ 250 kW, pulse frequency
2 kHz) are connected to interface X101 and two Motor Modules (400 V, output > 250 kW,
pulse frequency 1.25 kHz) are connected to interface X102.
Note
The offline topology automatically generated in the STARTER commissioning tool must be
manually modified, if this topology was wired.
Figure 12-21 Drive line-up in chassis format with different pulse frequencies
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Basic information about the drive system
12.10 Rules for wiring with DRIVE-CLiQ