Access protection and rights

6.28.4.1

SINAMICS access protection

The specified settings of the Write and know-how protection (Page 925) including password
protection also apply for access via the Web server to the drive parameters and
configuration. The Web server cannot be used to bypass this protection.
If access is not possible because of these settings, a corresponding message text is
displayed on the Web pages.
In addition to the SINAMICS access protection, access via the functions of the Web server is
restricted by other measures: See Additional access protection (Page 383).
6.28.4.2

Additional access protection

Further access restrictions
In addition to the SINAMICS access protection, access via the functions of the Web server is
restricted by other measures: An additional protection concept is used for two ever-present
users. The following access settings are specified per default:
● User 1 (diagnostics user): Name of the user: "SINAMICS"
● User 2 (parameterization user): Name of the user: "Administrator"
Note
Access rights during commissioning
During the commissioning phase, a login is not required to call the Web server. During this
phase, you have full access rights to all functions of the Web server like the "Administrator".
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Read access rights and the right to acknowledge faults.
Access rights to change the system and project and the right to acknowledge faults.
Basic functions
6.28 Web server
383