Parameter Description
P0776[2]

Type of DAC

CStat:
CT
P-Group: TERMINAL
Defines type of analog output.
Possible Settings:
0
Current output
1
Voltage output
Index:
P0776[0] : Analog output 1 (DAC 1)
P0776[1] : Analog output 2 (DAC 2)
Note:
The analog output is designed as a current output with a range of 0...20 mA.
For a voltage output with a range of 0...10 V an external resistor of 500 Ohms has to be connected at the
terminals (12/13 or 26/27).
P0777[2]

Value x1 of DAC scaling

CStat:
CUT
P-Group: TERMINAL
Defines x1 output characteristic in [%]. Scaling block is responsible for adjustment of output value defined in
P0771 (DAC connector input).
Parameters of DAC scaling block (P0777 ... P0781) work as follows:
Output signal (mA)
20
P0780
y
2
P0778
y
1
0
Where:
Points P1 (x1, y1) and P2 (x2, y2) can be chosen freely.
Index:
P0777[0] : Analog output 1 (DAC 1)
P0777[1] : Analog output 2 (DAC 2)
Example:
The default values of the scaling block provides a scaling of:
P1: 0.0 % = 0 mA
P2: 100.0 % = 20 mA
Dependency:
Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to
be generated.
94
Datatype: U16
Active: first confirm
Datatype: Float
Active: first confirm
P0777
P0779
x
x
1
2
Min:
Unit: -
Def:
QuickComm.: No
Max:
Min:
Unit: %
Def:
QuickComm.: No
Max:
%
100 %
MICROMASTER 440
Issue 01/06
Level
0
2
0
1
Level
-99999.0
2
0.0
99999.0
Parameter List
6SE6400-5BB00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents