Parameter Description
P1060[3]

JOG ramp-up time

CStat:
CUT
P-Group: SETPOINT
Sets jog ramp-up time. This is the time used while jogging is active.
JOG
f (Hz)
f max
(P1082)
P1058
0
Index:
P1060[0] : 1st. Drive data set (DDS)
P1060[1] : 2nd. Drive data set (DDS)
P1060[2] : 3rd. Drive data set (DDS)
Notice:
Ramp times will be used as follows:
-
P1060 / P1061 : JOG mode is active
-
P1120 / P1121 : Normal mode (ON/OFF) is active
-
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
P1061[3]

JOG ramp-down time

CStat:
CUT
P-Group: SETPOINT
Sets ramp-down time. This is the time used while jogging is active.
JOG
f (Hz)
f max
(P1082)
P1058
0
Index:
P1061[0] : 1st. Drive data set (DDS)
P1061[1] : 2nd. Drive data set (DDS)
P1061[2] : 3rd. Drive data set (DDS)
Notice:
Ramp times will be used as follows:
-
P1060 / P1061 : JOG mode is active
-
P1120 / P1121 : Normal mode (ON/OFF) is active
-
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
124
Datatype: Float
Active: first confirm
t
up
P1060
Datatype: Float
Active: first confirm
t
down
P1061
Min:
0.00
Unit: s
Def:
10.00
QuickComm.: No
Max:
650.00
t (s)
P
1058
=
P1060
t
up
P1082
Min:
0.00
Unit: s
Def:
10.00
QuickComm.: No
Max:
650.00
t (s)
P
1058
=
t
down
P1082
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
2
Level
2
P1061
Parameter List