Bi: Change To Torque Control - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P1501[3]

BI: Change to torque control

CStat:
CT
P-Group: CONTROL
Selects command source from which it is possible to change between master (speed control) and slave
(torque control).
r1170
Freq. setpoint
r0063
Act. frequency
CI: Torque setp.
P1503.C
(0:0)
BI:-> torque ctrl .
P1501.C
(0:0)
CI: Add. trq. setp
P1511.C
(0:0)
*) only active, if pre-control is enabled
(P1496 > 0)
Index:
P1501[0] : 1st. Command data set (CDS)
P1501[1] : 2nd. Command data set (CDS)
P1501[2] : 3rd. Command data set (CDS)
Caution:
If direct selection of torque control is used (P1300=22, 23) the OFF1 command is recognized as OFF2.
However, the OFF1 command is not recognized when torque control is selected indirectly (P1300=20, 21
and P1501=1). If indirect selection of torque control is used, it is recommended to program an OFF2
command using, for example a digital input or create the following circuit using the Free Function Blocks
(FFB):
Source
Torque switch-over
Source
ON/OFF1
Details:
Speed control with encoder feedback see P1460
Speed control without encoder feedback see P1470
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U32
Active: first confirm
Pre-
control
K
p
*)
Speed
controller
T
i
P1501
1
Parameter Description
Min:
Unit: -
Def:
QuickComm.: No
Max:
Droop
0
T
n
PI
r1538
r1539
r1508
T
i
SLVC:
P1452
VC:
P1442
&
P0840
Level
0:0
3
0:0
4000:0
r1518
r1538
Torque
setpoint
r1539
r0079
r1515
K
T
p
n
P1470
P1472
P1460
P1462
P0844
OFF2
1
ON/OFF1
175