A0920 Adc Parameters Not Correctly Set; A0921 Dac Parameters Not Set Properly; A0922 No Load At The Inverter; A0923 Jog Counter-Clockwise As Well As Jog Clockwise Are Requested - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06

A0920 ADC parameters not correctly set

Cause
ADC parameters should not be set to identical values, as this would lead to illogical results.
-
Index 0: Parameter settings for output identical.
-
Index 1: Parameter settings for input identical.
-
Index 2: Parameter settings for input do not correspond to ADC type.

A0921 DAC parameters not set properly

Cause
-
DAC parameters (P0777 and P0779) have identical values.
OR
-
DAC parameters (P0778 and P0780) have identical values.
Identical values would produce illogical results.
Diagnosis & Remedy
Check the following:
-
Output parameter settings. Ensure P0777 and P0779 are not identical.
-
Input parameter settings. Ensure P0778 and P0780 are not identical.

A0922 No load at the inverter

Cause
-
no load is connected to the inverter.
-
therefore several functions can run differently than under normal load conditions.

A0923 JOG counter-clockwise as well as JOG clockwise are requested

Cause
-
both JOG clockwise and JOG counter-clockwise (P1055/P1056) have been requested. This is the
reason that the RFG output frequency has been frozen to the actual value.
A0952 Load fault detected
Cause
-
load conditions at the motor indicate a load fault or mechanical fault.
Diagnosis & Remedy
Please check the following:
-
no braking, failure or destruction of the mechanical transmission line
-
if required, lubricate the mechanical transmission line.
If you are using an external encoder, please check the following parameter settings:
-
P2192 (delay time, load torque monitoring)
If you are using a specific speed range, then please check the following:
-
P2182 (load torque monitoring F1)
-
P2183 (load torque monitoring F1f2)
-
P2184 (load torque monitoring F1f3)
-
P2185 (upper torque threshold 1)
-
P2186 (lower torque threshold 1)
-
P2187 (upper torque threshold 2)
-
P2188 (lower torque threshold 2)
-
P2189 (upper torque threshold 3)
-
P2190 (lower torque threshold 3)
-
P2192 (delay time, load torque monitoring)
A0936 PID auto tuning active
Cause
-
PID auto tuning (P2350) is selected or is presently running.
Diagnosis & Remedy
-
after automatic PID optimization has been completed, the alarm is reset.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Faults and Alarms
319