Max. Frequency - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Parameter Description
P1082[3]

Max. frequency

CStat:
CT
P-Group: SETPOINT
Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. The
value set here is valid for both clockwise and anticlockwise rotation.
Futhermore, the monitoring function |f_act| >= P1082 (r0052 Bit10, see example below) is affected by this
parameter.
Index:
P1082[0] : 1st. Drive data set (DDS)
P1082[1] : 2nd. Drive data set (DDS)
P1082[2] : 3rd. Drive data set (DDS)
Example:
f_act
P1082
P1082 - P2162
|f_act| ≥ P1082 (f_max)
r0052
Bit 10
Dependency:
The maximal value of motor frequency P1082 is limited to pulse frequency P1800. P1082 is dependent on
the derating characteristic as followed:
f
P1082
max
If closed-loop vector control (P1300 > 19) is selected, then the maximum frequency is internally limited by
the following equation:
=
min(P1082,
f
max
The resultant value is displayed in r1084 (resultant maximum frequency).
The maximum output frequency of inverter can be exceeded if one of the following is active:
- p1335 ≠ 0
(Slip compensation active ) :
f
(p1335)
max
- p1200 ≠ 0
f
(p1200)
max
Note:
When using the setpoint source
-
Analog Input
-
USS
-
CB (e.g. PROFIBUS)
The setpoint frequency (in Hz) is cyclically calculated using a percentage value (e.g. for the analog input
r0754) or a hexadecimal value (e.g. for the USS r2018[1]) and the reference frequency P2000.
If for example P1082 = 80 Hz, P2000 = 50 Hz and the analog input is parameterised with P0757 = 0 V,
P0758 = 0 %, P0759 = 10 V, P0760 = 100 %, a setpoint frequency of 50 Hz will be applied at 10 V of the
analog input.
128
Datatype: Float
Active: first confirm
1
0
2 kHz
4 kHz
0 - 133.3 Hz
0 - 266.6 Hz
5
P0310,
200.00)
=
+
=
+
f
f
p1082
max
slip
,
max
(Flying restart active) :
=
+
=
f
2
f
p1082
max
slip
,
nom
Unit: Hz
QuickComm.: Yes
P1800
6 kHz
8 - 16 kHz
0 - 400 Hz
0 - 650 Hz
p1336
r0330
p0310
100
100
r0330
+
2
p0310
100
MICROMASTER 440
Issue 01/06
Level
Min:
0.00
1
Def:
50.00
Max:
650.00
t
t
Parameter List
6SE6400-5BB00-0BP0

Hide quick links:

Advertisement

Table of Contents