F0090 Signal loss, encoder

Quit
Refer to F0001
Cause
-
encoder signal between the encoder and inverter is interrupted
-
excessively large difference between the setpoint (reference) and actual frequency
Diagnosis & Remedy
Please check the following:
-
is there an integrated encoder? If there is no integrated encoder, then set P0400 = 0 and select the
operating mode sensorless closed-loop vector control (P1300 = 20 or 22)
-
the connection between the encoder and the inverter
-
is the encoder faulty? (select P1300 = 0, operation with fixed speed, check the encoder signal in r0061)
-
increase the encoder signal threshold in P0492, P0494

F0101 Stack overflow

Quit
Refer to F0001
Cause
-
software error or processor failure
Diagnosis & Remedy
-
carry-out self-test routines

F0221 PID feedback below the minimum value

Quit
Refer to F0001
Cause
-
PID feedback below the minimum value P2268.
Diagnosis & Remedy
-
change value of P2268.
-
set feedback gain.

F0222 PID feedback above maximum value

Quit
Refer to F0001
Cause
-
PID feedback above maximum value P2267.
Diagnosis & Remedy
-
change value of P2267.
-
set the feedback gain.
F0422 No load applied to inverter
Quit
Refer to F0001
Cause
No Load is applied to the inverter.
As a result, some functions may not work as under normal load conditions.
F0450 Failure BIST tests
Quit
Refer to F0001
Cause
Self-test routine unsuccessful (refer to fault value r0949):
-
r0949 = 1: Self-test routine for power module components unsuccessful
-
r0949 = 2: Self-test routine for closed-loop control module components unsuccessful
-
r0949 = 4: Several function tests were unsuccessful
-
r0949 = 8: Several tests carried-out at the I/O module were unsuccessful (only MICROMASTER 420)
-
r0949 = 16: Failure of the internal RAM at the switch-on test
Diagnosis & Remedy
-
the drive is functional, but several functions are not correctly executed.
-
replace the drive